(VTScada Applications Only)
Data Flow Module tags enable you to represent the installed modules for a Data Flow RTU. A set of 37 of these tags has been pre-configured for you to represent digital control modules, digital monitor modules, analog control modules, digital monitor modules, digital pulse modules, and TacPac modules. You cannot create a new fully-configured Data Flow Module tag using the tag browser.
Numbers of points by module type:
• Digital Monitor Modules (DMM) have 12 digital input points
• Digital Control Modules (DCM) have 8 output and 4 input points (for the DCM001 and DCM011) or 4 output and 8 input points (for DCM002 and DCM012)
• Analog Monitor Modules (AMM) have 4 analog input points
• Analog Control Modules (ACM) have 4 analog output points
• TacPac Digital Input Modules have 12 digital input points
• TacPac 12-bit Control Modules have 12 digital output points
• TacPac 32-bit Digital Input Modules have 32 digital input points
The Data Flow module has the following characteristics:
Data Flow Module Characteristics
Tag Browser Name: Data Flow Module
Database Table Name: DFModule
Type: Input/Output Tag
Tag Group Memberships: None
Log Enabled Variables: None
Native Drawing Methods: Data Flow Module Tag Drawing Methods (VTScada)
Topics in this section:
Data Flow Module Tag Type Properties: ID