There are six standard alarm lists in the Alarm Manager database. These are:
|
Alarm List |
Index |
Internal or Logged |
|
Current alarm list (a merge of active and unacknowledged lists) |
-2 |
Logged |
|
All configured alarms |
-1 |
Logged |
|
Log or history of alarms |
0 |
Internal |
|
Active alarms |
1 |
Internal |
|
Unacknowledged alarms |
2 |
Internal |
|
Disabled alarms |
3 |
Internal |
|
User-defined alarm lists |
4 + |
User-defined |
Note: By default, the "Current" list is displayed on the default Alarm page; however, you can customize the list to be displayed by default using the AlmPgStartListINIAlarms configuration setting. For a full list of configuration settings related to alarms, see Config.ini [ALARM_MANAGER] Section Variables.