Analog Output Tags

Counted towards your tag license limit.

This is a legacy tag type. You are advised to use the I/O and Calculations Tag instead.
Use this legacy type only if you are certain that it contains unique features that are absolutely necessary to your work.

It is the role of analog outputs to take analog data from the user or from another tag, and write it to an I/O device. Analog data can be transmitted by an operator via a slider or a numeric entry field.

In most situations, use Analog Control Tags rather than Analog Output tags.

Retained or Persisted values

Analog Control and Analog Output tags will both retain their last written value across application restarts. Use these tags when there is a need for a value to persist.

String I/O tags with output enabled, and with no driver ("No tag selected" rather than the default, "[*Driver] None found") will retain their last written value across application restarts.

The Digital Control and Digital Output tags do not have a similar feature, but an analog tag can be used in their place, writing a zero or a one. If the intent is to write a clear zero or one with an analog tag, both the scaled and unscaled range should be adjusted for a minimum value of zero and a maximum value of one, so that scaling does not adjust the values.

Analog Output properties I/O tab

The I/O tab holds the properties used to identify and establish a connection to the communication driver tag being used to exchange data with your physical I/O device (e.g. PLC or RTU). This is done by identifying the communication driver tag that communicates with the physical I/O device, the address at the physical I/O device from which this tag is to read its data, and the rate at which the I/O device should be scanned for data.

I/O Device

Select the communication driver tag to which data will be written.

By default, the tag will look for a parent tag that is a device driver (..\*Driver). If none is found, the text "--Missing--" will be displayed. The tag button to the right of the field opens the tag browser, from which you can either select an existing communication driver tag or add a new one. The X button will clear the field. Right-clicking on a tag in the field will open a dialog with which you can add or remove a Snapshot Expression, or open a selected driver's properties dialog.

Address

Provide the address within the I/O device to which this tag is to write data. This value must match the configuration of your PLC or RTU hardware. Refer to the Addressing topic for your particular device driver for guidance.

For some drivers (SNMP and the OPC Client) an address browser is provided to assist you.

Engineering Units

Provide units of measure that the input data represents. Possible values for this field include "rpm" "degrees C", "%", etc

Data Source

The value output by an analog control can be supplied by an operator via a widget on the screen, it can be supplied by a data source, or both can be used.

Normally, the data source would be another tag or an expression. If both a data source and an operator control are provided, then the value of the control tag will be whichever value was most recently set.

Use Data Source for display only

The data source can be used either as the value of the tag, updating the tag's value whenever the data source changes, or it can be used for display purposes only, leaving the value output by the tag unchanged. Use this check box to select one mode or the other.

Analog Output properties Scaling tab

The Scaling tab requires values that will be used to convert unscaled, raw data from the I/O device associated with this tag into scaled data that will be reported to operators. VTScada uses an algorithm to calculate this tag's value internally, based on the known unscaled and scaled values you supply.

The default value for each of these fields is stored in an application property. You are advised to change those properties to match the values used by your hardware by using the Edit Properties page of the Application Configuration dialog.

You will need to use the Advanced mode of the properties page. The properties to copy and edit are:

  • AnalogUnscaledMinDefault
  • AnalogUnscaledMaxDefault
  • AnalogScaledMinDefault
  • AnalogScaledMaxDefault

I/O scaling illustrated

VTScada assumes a linear relationship between the values as shown. The scaled and unscaled process values you provide set the slope of the line, allowing any value on one axis to be mapped to the other.

The values do not limit what the tag can read, but the Scaled Process Min and Max values do limit what the tag can write.

Min and Max Unscaled Process Data (Required.)

Use these to tell VTScada the range of raw values to expect from or write to hardware.

Min and Max Scaled Process Data (Required.)

Values must correspond to the Unscaled Min and Max values. VTScada uses these to convert between engineering units displayed in the SCADA system and raw values read from or written to hardware.

Analog Output properties Owner tab

This tag can be used in an owner/contributor structure where multiple contributor tags can supply their values to an owner tag.

There is no specific "owner" tag type, rather an owner tag is typically a custom-designed tag that is created using VTScada scripting code.

Owner

Specify a tag to which this contributor should supply its data. An owner tag is one which you must design and then create, using the VTScada scripting language.

The owner tag may keep track of different aspects of each contributor's data, from the presence of a user-defined manual data value, to questionable data, according to the configuration of the check boxes appearing beneath the Owner field. These check boxes also determine the way that this contributor tag's value should be used in the owner tag's calculations.

Set Owner\DataX(…) to Value

When selected, the Set Owner\DataX[…] To Value check box is used to set the value of this contributor tag as the nth element in the owner tag's array. You may choose to set this contributor tag's value in more than one of the owner tag's array elements if required.

Set Active/Unack. Priority

An owner tag may keep track of the alarm priority and status of its contributors. When selected, the Set Active/Unack. Priority check box causes the owner tag to keep track of the priority of the contributor's active alarm (or records an Invalid if the contributor is not in an alarm state). Selecting the Set Active/Unack. Priority check box also causes the owner tag to record whether the alarm has been acknowledged.

Record Use of Manual Data

An owner tag may keep track of the number of contributor tags that are providing manual data (user-defined values), rather than reading data from their I/O device. When selected, the Record Use of Manual Data check box is used to increment the owner's count of the number of tags that are contributing manual data by 1 when manual data has been provided for this contributor, and decrement this count by 1 when no manual data value has been specified.

Record Data Quality (Analog and Digital Input only)

An owner tag may keep track of the quality of the data for each of its contributors. When selected, the Record Tag Quality check box is used to increment the owner tag's count of the number of tags that are contributing quality data by 1, and decrement this count by 1 when this contributor is not supplying quality data.

Record Tag Validity

An owner tag may keep track of the questionable status of the data for each of its contributors. When selected, the Record Tag Validity check box is used to increment the owner tag's count of the number of tags that are contributing questionable data by 1, and decrement this count by 1 when this contributor is not supplying questionable data.

Analog Output properties Merit tab

Privilege

Select a custom security privilege (Protect Pages and Output Tags) from this drop down to limit the operation of this control to only those operators who have been granted the matching security privilege.

Questionable Data

Use the Questionable Data parameter to flag this tag’s data in the event that you suspect the values it is reporting might not be accurate, or when this tag has initially been created and you wish to ensure that its data is marked for extra monitoring.

Analog Output properties Display tab

When this tag is represented on screen by widgets that can use a Style Settings tag, you can save development time by choosing the Style Settings tag that holds the correct display configuration for this tag instance.

The default configuration will use System Style, the default style tag that is automatically part of every new VTScada application.

Analog Output properties Alarm tab

Use the Alarm tab to create new Alarm tags that will be triggered by this tag. The Add button will open a configuration panel for a new Alarm tag. The triggered-by field for the new alarm will automatically be linked to this tag’s value. The new alarm tags will be created as children of the current tag.

Analog Output properties Script tab

Optionally, link one or more Script tags to this tag. A Script tag provides a means of creating a procedure, using VTScada’s programming language, that will run whenever this tag’s value changes.

Analog Output properties Logger tab

Use the logger tab to associate a single Logger tag with this tag. The Logger tag will work with the attached Historian to record this tag’s data to disk so that it can be plotted on the Historical Data Viewer page. The new logger tag will be created as a child of the current tag.

Note: It is recommended that only one Logger tag be directly associated with a single input or output tag. If you require multiple loggers with different logging rates, please refer to Using Function Tags to Create Multiple Data Logs of an I/O Tag

Confirmation Prompts for Output Tags - Control options for confirmation prompt text.