IEC Error Codes
Error code (Decimal) |
Error code (Hex) |
Meaning |
---|---|---|
257 | 0x101 | Serial Port Parameter(s) Out Of Range |
258 | 0x102 | Serial Port Not Active |
259 | 0x103 | TCP/IP Port Failed to Connect |
260 | 0x104 | TCP/IP Port Disconnected |
261 | 0x105 | Serial Port inactivity timeout |
511 | 0x1FF | Communication channel not available |
512 | 0x200 | Data Link - Invalid Command |
513 | 0x201 | Data Link - Timed Out Waiting For Echo |
514 | 0x202 | Data Link - No Reply |
515 | 0x203 | Data Link - No Acknowledge |
516 | 0x204 | Data Link Reset - No Acknowledge |
517 | 0x205 | Tag Address not configured in the device |
518 | 0x206 | Failed to synchronize time |
768 | 0x300 | ASDU Address Error |
769 | 0x301 | ASDU Type Address Error |
770 | 0x302 | Information Object Address Error |
771 | 0x303 | QOC Address Error |
772 | 0x304 | ASDU Type Out of Range |
773 | 0x305 | ASDU Address Out Of Range |
774 | 0x306 | Info Object Address Out Of Range |
776 | 0x308 | Data unavailable |
777 | 0x309 | Unknown ASDU Type |
778 | 0x30A | Unknown cause of transmission |
779 | 0x30B | Unknown common address of ASDU |
780 | 0x30C | Unknown information object address |
781 | 0x30D | Incorrect response to select command |
782 | 0x30E | Incorrect response to execute command |
783 | 0x30F | Incorrect response - no CON received |
784 | 0x310 | Incorrect response to GI Poll |
785 | 0x311 | Invalid Header Byte |
786 | 0x312 | Timeout Waiting for Length |
787 | 0x313 | Invalid Message Length |
788 | 0x314 | Timeout waiting for APCI |